0.1.0a45 — readings you can trust, and the discharge windows
If your battery's lifetime charge reads in the millions of kWh, this is the
fix: a counter past a million kWh is refused rather than published, and one a
wrap short is caught by what it contains. Seen on every SH10RS on
B000.V002.P067. Thanks to Maximo101 for the diagnosis that found it.
Also here:
- The discharge windows are controls on SAPPHIRE-H_B001.V000.P020 and P022,
where a watched run saw them obey: four windows a day, each edge a time
entity with an "all day" switch, and the weekend enable. - A wallbox now says whether an inverter manages it, inferred from what the
inverter writes to it. Whether its own registers may be written stays your
answer, in the entry's options. - A managed wallbox's current is bounded by the rating the wallbox itself
reports, instead of a flat 32 A. - Clearing the capability test's history no longer throws away the readings
it has collected, only the runs. - The daily-counter check reads the inverter's own clock, so a Home Assistant
in a different timezone no longer reports a correct midnight reset as a
fault. Measured on an SH10RT on P020: all eight daily counters reset in one
poll, at the inverter's midnight. - A floating MPPT input is no longer called a string: the check asks for
current beside the voltage.
Install: Settings → Marketplace, or update the preview repository.