github ffind-dev/pve-ups v3.3.0

8 hours ago

Added

  • Vendor MIB support, starting with APC PowerNet. An SNMP UPS is no longer read only
    through RFC 1628. Every SNMP UPS has a new MIB setting — Automatic (default),
    RFC 1628 (standard) or APC PowerNet — and the poller carries a table-driven profile
    per MIB, so further vendors are a table rather than new code.
  • Automatic needs no configuration and is what existing UPS entries get on update: the
    regular poll carries the vendor anchor object alongside the standard ones, and the UPS
    is read on the vendor MIB as soon as it answers there. Under SNMPv1, where a single
    missing object aborts the whole request, the poller retries on the vendor MIB instead.
  • This makes APC cards work that could not be used before: Schneider only supports
    RFC 1628 on Network Management Card 2 (AP9630/AP9631/AP9635) from firmware sumx/sy
    v5.1.7 on, while the older NMC1 cards (AP9617/AP9618/AP9619) speak PowerNet only.
  • Cards that support both are now more accurate as well. upsAdvBatteryRunTimeRemaining
    is reported in hundredths of a second instead of whole minutes, and PowerNet reports a
    self-test (onBatteryTest) as its own state — RFC 1628 cannot tell one apart from a
    real outage.
  • The UPS test walks both MIBs in Automatic mode and says which one it settled on and
    why, so "nothing works" becomes "this card has no RFC 1628, but PowerNet answers every
    object". The dashboard names the MIB a UPS is being read on.